450/750V SR Insulated & Overall Screened Control Cables (2-4 Cores & Multicores)
FFX200 07SOZ1-F (PH30/60)(CU/SR/OSCR/LSZH 450/750V Class 5)
APPLICATION
The cables are designed, manufactured and tested for general application in power and signal wiring, for emergency circuit and fire circuit control where high rejection to electrostatic noise is needed
STANDARDS
- Basic design adapted to BS 7629-1
FIRE PERFORMANCE
Circuit Integrity |
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
Circuit Integrity with mechanical shock |
EN 50200(PH30/60); CEI 20-36/4-0 |
Circuit Integrity with mechanical shock & water spray |
EN 50200 annex E |
System circuit integrity |
DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24;VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
450/750 V
CABLE CONSTRUCTION
Conductors |
Plain annealed copper wire, flexible according to IEC 60228 class 5 |
Insulation |
Fire resistant special ceramized silicone rubber compound type EI2 as per BS 7655-1.1 |
Cabling |
The cores are cabled together in concentric layers with suitable non-hygroscopic fillers |
Overall screen |
Aluminum/polyester tape with tinned copper drain wire |
Sheath |
Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option |
COLOUR CODE
Insulation Colour as per BS 7629
Number of cores |
Core colours or numbering |
2 cores+uninsulated circuit protective conductor |
Brown, Blue or Brown, Brown |
3 cores+uninsulated circuit protective conductor |
Brown, Black, Grey |
4 cores+uninsulated circuit protective conductor |
Brown, Blue, Black, Grey |
7, 12 and19 cores+uninsulated drain wire |
Numbers 1, 2, 3, 4, 5, 6, 7 and upwardsor, for identification by colour, an identicalcolour(excluding brown and black),except for twoadjacent cores in each layer distinctively colouredbrown and black. |
Sheath Colour: Orange (other colours upon request)
PHYSICAL AND THERMAL PROPERTIES
Temperature range during operation (fixed state) |
-30°C – +90°C |
Temperature range during installation (mobile state) |
-20°C – +50°C |
Minimum bending radius |
7.5 x Overall Diameter |
ELECTRICAL PROPERTIES
Dielectric test |
2000 V r.m.s. x 5' (core/core) |
Insulation resistance |
≥300 MΩ x km (at 20°C) |
Short circuit temperature |
350°C |
CONSTRUCTION PARAMETERS
Cable Code |
No. of Core X Cross Section |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Approx. Weight |
|
mm2 |
mm |
mm |
mm |
kg/km |
2 Cores |
FFX200 07SOZ1-K(PH30/60) 2G0.75 |
2x0.75 |
0.7 |
0.9 |
7,6 |
69 |
FFX200 07SOZ1-K(PH30/60) 2G1.0 |
2x1.0 |
0.7 |
1.0 |
8,0 |
78 |
FFX200 07SOZ1-K(PH30/60) 2G1.5 |
2x1.5 |
0.8 |
1.0 |
8,3 |
88 |
FFX200 07SOZ1-K(PH30/60) 2G2.5 |
2x2.5 |
0.9 |
1.1 |
9,8 |
123 |
3 Cores |
FFX200 07SOZ1-K(PH30/60) 3G0.75 |
3x0.75 |
0.7 |
0.9 |
8,0 |
84 |
FFX200 07SOZ1-K(PH30/60) 3G1.0 |
3x1.0 |
0.7 |
1.0 |
8,2 |
86 |
FFX200 07SOZ1-K(PH30/60) 3G1.5 |
3x1.5 |
0.8 |
1.0 |
8,8 |
112 |
FFX200 07SOZ1-K(PH30/60) 3G2.5 |
3x2.5 |
0.9 |
1.1 |
10,4 |
159 |
4 Cores |
FFX200 07SOZ1-K(PH30/60) 4G0.75 |
4x0.75 |
0.7 |
1.0 |
8,7 |
103 |
FFX200 07SOZ1-K(PH30/60) 4G1.0 |
4x1.0 |
0.7 |
1.1 |
8,9 |
110 |
FFX200 07SOZ1-K(PH30/60) 4G1.5 |
4x1.5 |
0.8 |
1.1 |
9,8 |
141 |
FFX200 07SOZ1-K(PH30/60) 4G2.5 |
4x2.5 |
0.9 |
1.2 |
11,4 |
196 |
7 Cores |
FFX200 07SOZ1-K(PH30/60) 7G1.0 |
7x1.0 |
0.7 |
1.1 |
10,8 |
176 |
FFX200 07SOZ1-K(PH30/60) 7G1.5 |
7x1.5 |
0.8 |
1.2 |
11,7 |
218 |
FFX200 07SOZ1-K(PH30/60) 7G2.5 |
7x2.5 |
0.9 |
1.3 |
13,4 |
305 |
12 Cores |
FFX200 07SOZ1-K(PH30/60) 12G1.0 |
12x1.0 |
0.7 |
1.2 |
13,9 |
275 |
FFX200 07SOZ1-K(PH30/60) 12G1.5 |
12x1.5 |
0.8 |
1.3 |
15,3 |
352 |
FFX200 07SOZ1-K(PH30/60) 12G2.5 |
12x2.5 |
0.9 |
1.5 |
17,9 |
505 |
19 Cores |
FFX200 07SOZ1-K(PH30/60) 19G1.0 |
19x1.0 |
0.7 |
1.4 |
16,4 |
408 |
FFX200 07SOZ1-K(PH30/60) 19G1.5 |
19x1.5 |
0.8 |
1.5 |
18,2 |
535 |
FFX200 07SOZ1-K(PH30/60) 19G2.5 |
19x2.5 |
0.9 |
1.6 |
21,1 |
760 |
ELECTRICALl PROPERTIES
Conductor Operating Temperature |
90°C |
Ambient Temperature |
30°C |
Current-Carrying Capacities (Amp)
Conductor
cross-sectional
area |
Reference Method A
(enclosed in conduit in thermally
insulating wall etc) |
Reference Method B
(enclosed in conduit on a wall
or in trunking etc) |
Reference Method C
(clipped direct) |
Reference Method E
(in free air or on aperforated cable tray,
horizontal or vertical etc) Touching |
1 two-core cable*,
single-phase a.c. or d.c. |
1 three-or four corecable*,
three-phase a.c. |
1 two-core cable*,
single-phase a.c. or d.c. |
1 three-or four corecable*,
three-phase a.c. |
1 two-core cable*,
single-phase a.c. or d.c. |
1 three-or four corecable*,
three-phase a.c. |
1 two-core cable*,
single-phase a.c. or d.c. |
1 three-or four corecable*,
three-phase a.c. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
0.75 |
|
|
|
|
|
|
|
|
1.0 |
14.5 |
13 |
17 |
15 |
19 |
17 |
21 |
18 |
1.5 |
18.5 |
16.5 |
22 |
19.5 |
24 |
22 |
26 |
23 |
2.5 |
25 |
22 |
30 |
26 |
33 |
30 |
36 |
32 |
4 |
33 |
30 |
40 |
35 |
45 |
40 |
49 |
42 |
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectional area |
Two-core cables, d.c. |
Two-core cable, single-phase a.c. |
Three-or four core cable,three-phase a.c. |
1 |
2 |
3 |
4 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
0.75 |
|
|
|
1.0 |
46 |
46 |
40 |
1.5 |
31 |
31 |
27 |
2.5 |
19 |
19 |
16 |
4 |
12 |
12 |
10 |